Technical Data
W
L
H
General Data
Inputs
Number/Type
4
inputs for 2- or 3-wire sensors (PNP), DC
Supply
from AS-Interface (switch position INT, basic setting) or external U
EXT
(
switch
position EXT)
Voltage
21 ... 31
V DC (INT)
Current loading capacity
150
mA, overload- and short-circuit protected (INT)
Ambient temperature
-25 ... 60
°C (-13 ... 140 °F)
Protection degree
IP20
Mounting
DIN rail
VAA-4E4A-KE-ZE/R
VAA-4E4A-KE-ZEJQ/E2L
VBA-4E3A-KE-ZE/R
VBA-4E3A-KE-ZEJQ/E2L
VBA-4E4A-KE-ZE/R
VBA-4E4A-KE-ZEJQ/E2L
VBA-4E-KE-ZEJQ
Slave type
A/B slave
● ● ● ● ●
Standard slave
● ●
Required master specification
V2.0
● ●
V2.1
● ●
●
V3.0
● ●
UL File Number
E106378
●
●
●
E87056
●
●
● ●
Rated operational current
30
mA (without sensors) / max. 180 mA
●
35
mA (without sensors) / max. 190 mA
●
●
●
35
mA (without sensors)/max. 210 mA
●
●
35
mA (without sensors) / max. 235 mA
●
Inputs
Input current
8
mA (limited internally)
●
●
●
9
mA (limited internally)
●
●
● ●
Outputs
Number/Type
3
electronic outputs, PNP, overload
and short-circuit proof
●
3
relay outputs, normally open
●
4
electronic outputs, PNP, overload
and short-circuit proof
●
●
4
relay outputs, normally open
●
●
Supply
from external auxiliary voltage U
AUX
●
●
●
none
●
●
●
Current
O1 max. 3 A, O2/O3 max. 1.5 A, total 6
A (T
B
40
°C)
O1 max. 2 A, O2/O3 max. 1 A, total 4 A
(
T
B
60
°C)
●
2
A per output, sum 4A (T
B
40
°C)
0.5
A per output, total 2A (T
B
60
°C,
arranged in series without gaps)
2
A per output, total 4A (T
B
60
°C,
arranged in series with 5 mm gap)
●
●
Voltage
(
U
AUX
- 0.5
V)
●
●
●
Profile
S-0.A.0
●
S-7.A.0
● ●
S-7.A.7
● ●
S-7.0
● ●
Dimensions
Length L [mm]
102
Width W [mm]
22,5
Height H [mm]
99
VBP-HH1-V3.0-KIT
AS-Interface Handheld with accessory
VBP-HH1-V3.0
AS-Interface Handheld
VAZ-PK-1,5M-V1-G
Connection cable module/hand-held programming device
VBP-HH1-V3.0-V1
AS-Interface Handheld
This and more accessories can be found in chapter 7.6 from page 893
See pages from 974 ... for cordsets
See pages 1074 ... for mounting aids
Accessories
AS-Interface sensor/actuator modules
4
PNP inputs / versions with 3 and
4
electronic or relay outputs
Standard and A/B slave versions
IP20
Color coded, removable terminals
speed up installation and
replacement
Relay version allows switching of
115/230
VAC sources
Increased application flexibility as
connected sensors are powered
from AS-Interface or external po-
wer source (DIP switch selectable)
Properties