Germany: +49 621 776-4411
Subject to modifications without notice
Pepperl+Fuchs Group
fa-info@pepperl-fuchs.com
USA: +1 330 486 0001
fa-info@us.pepperl-fuchs.com
Singapore: +65 6779 9091
fa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Date of issue: 0801/2012
885
For detailed data and product description refer to the data sheets at
AS-Interface,
Modules
7
.4
Technical Data
W
L
H
General Data
UL File Number
E223772
Protection degree
IP20
Mounting
DIN rail
Model Number
VBA-2A-KE2-I/U
VBA-2E-KE2-I/U
VBA-2E-KE2-I/U-V3.0
Slave type
A/B slave
●
Standard slave
●
●
Required master specification
V2.1
●
●
V3.0
●
Rated operational current
80
mA
●
●
Supply via AS-Interface:
100
mA
supply via AS-Interface and U
AUX
:
120
mA
●
Inputs
Input voltage
For voltage module:
25
V per input
●
Number/Type
2
analog inputs
Current: 4 ... 20 mA
voltage: 0 ... 10 V
●
●
Supply
from AS-Interface or from external auxi-
liary voltage as required U
AUX
●
●
Current loading capacity
40
mA per input
●
Input current
For current module:
40
mA per input
●
Outputs
Number/Type
2
analog outputs
Current: 4 ... 20 mA ± 0.5 %
voltage: 0 ... 10 V ± 0.5 %
●
Open loop voltage
current output: max. 21 V (dependent
on the supply voltage)
●
Supply
from AS-Interface or from external auxi-
liary voltage as required U
AUX
●
Profile
S-7.A.9
●
S-7.3.D
●
S-7.3.5
●
Ambient temperature
0 ... 55
°C (32 ... 131 °F)
●
0 ... 70
°C (32 ... 158 °F)
●
●
Dimensions
Length L [mm]
99,6
Width W [mm]
22,5
Height H [mm]
85
VBP-HH1-V3.0-KIT
AS-Interface Handheld with accessory
VBP-HH1-V3.0
AS-Interface Handheld
VAZ-PK-1,5M-V1-G
Connection cable module/hand-held programming device
VBP-HH1-V3.0-V1
AS-Interface Handheld
This and more accessories can be found in chapter 7.6 from page 893
See pages from 974 ... for cordsets
See pages 1074 ... for mounting aids
Accessories
AS-Interface analog modules
Versions with 4 PNP inputs and 2
analog inputs / versions with 2 and
4
electronic outputs
Standard and A/B slave versions
IP20
Selectable current or voltage
analog inputs or outputs increase
usability/flexibility
Color-coded removable terminals
simplify maintenance
Properties
Your Benefit