ICA-AI-RTD-IO-V1 |
Vendor ID |
1 (0x0001) |
 |
Vendor Name |
Pepperl+Fuchs |
Vendor Text |
Pepperl+Fuchs |
Vendor URL |
http://www.pepperl-fuchs.com/io-link |
Device ID |
984323 (0x0f0503) |
DeviceFamily |
Analog converter |
Features |
Block Parameter |
yes |
Data Storage |
yes |
Supported Access Locks |
Parameter: no, Data Storage: yes, Local Parameterization: no, Local User Interface: no |
Communication |
IO-Link Revision |
V1.1 |
Transmission Rate | 38400 bit/s (COM2) |
Minimum Cycle Time |
10 ms |
SIO Mode Supported |
no |
M-Sequence Capability | PREOPERATE = TYPE_0 with 1 octet on-request data OPERATE = TYPE_2_2 with 1 octet on-request data ISDU supported |
Device Variant |
ICA-AI-RTD-IO-V1 |
Description |
RTD analog to IO-Link converter, RTD analog input, configurable: PT100 (Climate), PT200, PT500, PT1000, 0 .. 3000 Ohm, M12 4-pin |
Product ID |
70163607 |
Device Icon |
 |
Device Symbol |
 |
Connection Type | M12-4 connector |
Connection Symbol |
 |
Connection Description |
Plug, M12, 4-pin |
- pin 1 |
brown; L+ |
- pin 2 |
white; NC |
- pin 3 |
(light) blue; L- |
- pin 4 |
black; C/Q |
subindex |
bit offset |
data type |
allowed values |
default value |
acc. restr. |
mod. other var. |
excl. from DS |
name |
description |
1 |
120 |
8-bit UInteger |
|
|
ro |
|
|
Reserved |
|
2 |
112 |
8-bit UInteger |
|
|
ro |
|
|
Master Cycle Time |
Communication: Current communication cycle duration used by the master. This value defines the process data cycle. |
3 |
104 |
8-bit UInteger |
|
|
ro |
|
|
Min Cycle Time |
Communication: Minimum communication cycle duration supported by the device. This value defines the lowest possible process data cycle. |
4 |
96 |
8-bit UInteger |
|
|
ro |
|
|
M-Sequence Capability |
Communication: Information on the structure and the supported features of the communication messages. |
5 |
88 |
8-bit UInteger |
|
17 |
ro |
|
|
IO-Link Revision ID |
Communication: Identifier for the currently used communication protocol revision. |
6 |
80 |
8-bit UInteger |
|
|
ro |
|
|
Process Data Input Length |
Communication: Information on width and features of the process input data (Process Data from Device to Master). |
7 |
72 |
8-bit UInteger |
|
|
ro |
|
|
Process Data Output Length |
Communication: Information on width of the process output data (Process Data from Master to Device). |
8 |
64 |
8-bit UInteger |
|
|
ro |
|
|
Vendor ID 1 |
Identification: Highest octet of the Vendor ID. Combined with the parameter Vendor ID 2, this parameter defines the 16-bit value of the unique Vendor ID as assigned by the IO-Link Community. |
9 |
56 |
8-bit UInteger |
|
|
ro |
|
|
Vendor ID 2 |
Identification: Lowest octet of the Vendor ID. Combined with the parameter Vendor ID 1, this parameter defines the 16-bit value of the unique Vendor ID as assigned by the IO-Link Community. |
10 |
48 |
8-bit UInteger |
|
|
ro |
|
|
Device ID 1 |
Identification: Highest octet of the Device ID. Combined with the parameters Device ID 2 and 3, this parameter defines the 24-bit value of the vendor-specific Device ID. |
11 |
40 |
8-bit UInteger |
|
|
ro |
|
|
Device ID 2 |
Identification: Middle octet of the Device ID. Combined with the parameters Device ID 1 and 3, this parameter defines the 24-bit value of the vendor-specific Device ID. |
12 |
32 |
8-bit UInteger |
|
|
ro |
|
|
Device ID 3 |
Identification: Lowest octet of the Device ID. Combined with the parameters Device ID 1 and 2, this parameter defines the 24-bit value of the vendor-specific Device ID. |
13 |
24 |
8-bit UInteger |
|
|
ro |
|
|
Reserved |
|
14 |
16 |
8-bit UInteger |
|
|
ro |
|
|
Reserved |
|
15 |
8 |
8-bit UInteger |
|
|
ro |
|
|
Reserved |
|
16 |
0 |
8-bit UInteger |
|
|
wo |
X |
|
System Command |
Application: Command interface for devices without ISDU support. Validity and execution of commands are not confirmed. |
subindex |
bit offset |
data type |
allowed values |
default value |
acc. restr. |
mod. other var. |
excl. from DS |
name |
description |
1 |
120 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 1 |
|
2 |
112 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 2 |
|
3 |
104 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 3 |
|
4 |
96 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 4 |
|
5 |
88 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 5 |
|
6 |
80 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 6 |
|
7 |
72 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 7 |
|
8 |
64 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 8 |
|
9 |
56 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 9 |
|
10 |
48 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 10 |
|
11 |
40 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 11 |
|
12 |
32 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 12 |
|
13 |
24 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 13 |
|
14 |
16 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 14 |
|
15 |
8 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 15 |
|
16 |
0 |
8-bit UInteger |
|
|
|
|
|
Device-specific Parameter 16 |
|
subindex |
bit offset |
data type |
allowed values |
default value |
acc. restr. |
mod. other var. |
excl. from DS |
name |
description |
1 |
0 |
Boolean |
false = Unlocked, true = Locked |
|
|
|
|
Parameter Write Access |
This lock prevents the write access to all read/write parameters of the device except for the parameter 'Device Access Locks'. |
2 |
1 |
Boolean |
false = Unlocked, true = Locked |
0 |
|
|
|
Data Storage |
This lock prevents the write access to the device parameters via the data storage mechanism. |
3 |
2 |
Boolean |
false = Unlocked, true = Locked |
|
|
|
|
Local Parameterization |
This lock prevents the device settings from being changed via local operating elements on the device. |
4 |
3 |
Boolean |
false = Unlocked, true = Locked |
|
|
|
|
Local User Interface |
This lock prevents the access to the device settings and display via a local user interface. The user interface is disabled. |
subindex |
bit offset |
data type |
allowed values |
default value |
acc. restr. |
mod. other var. |
excl. from DS |
name |
description |
1 |
0 |
Boolean |
false = Disabled, true = Enabled |
|
|
|
|
Reserved |
|
2 |
1 |
Boolean |
false = Disabled, true = Enabled |
true |
|
|
|
Warning Threshold Underrun |
Enabled: an event is generated if the process data value is below the configured lower value of the warning threshold. |
3 |
2 |
Boolean |
false = Disabled, true = Enabled |
true |
|
|
|
Warning Threshold Overrun |
Enabled: an event is generated if the process data value is above the configured upper value of the warning threshold. |
4 |
3 |
Boolean |
false = Disabled, true = Enabled |
true |
|
|
|
Temperature Overrun |
Enabled: an event is generated if the device ambient temperature is above the specified temperature range. |
5 |
4 |
Boolean |
false = Disabled, true = Enabled |
true |
|
|
|
Supply Voltage Overrun |
Enabled: an event is generated if the supply voltage is Ub > 30V. |
6 |
5 |
Boolean |
false = Disabled, true = Enabled |
true |
|
|
|
Supply Voltage Underrun |
Enabled: an event is generated if the supply voltage is Ub < 18V. |
7 |
6 |
Boolean |
false = Disabled, true = Enabled |
|
|
|
|
Reserved |
|
8 |
7 |
Boolean |
false = Disabled, true = Enabled |
|
|
|
|
Reserved |
|
9 |
8 |
Boolean |
false = Disabled, true = Enabled |
|
|
|
|
Reserved |
|
10 |
9 |
Boolean |
false = Disabled, true = Enabled |
|
|
|
|
Reserved |
|
11 |
10 |
Boolean |
false = Disabled, true = Enabled |
true |
|
|
|
Wire Break |
Enabled: an event is generated if the current loop to the connected device is interrupted. |
12 |
11 |
Boolean |
false = Disabled, true = Enabled |
|
|
|
|
Reserved |
|
13 |
12 |
Boolean |
false = Disabled, true = Enabled |
|
|
|
|
Reserved |
|
14 |
13 |
Boolean |
false = Disabled, true = Enabled |
|
|
|
|
Reserved |
|
15 |
14 |
Boolean |
false = Disabled, true = Enabled |
true |
|
|
|
Analog Input Underrun |
Enabled: an event is generated if the analog input value is below the nominal range. |
16 |
15 |
Boolean |
false = Disabled, true = Enabled |
true |
|
|
|
Analog Input Overrun |
Enabled: an event is generated if the analog input value is above the nominal range. |
subindex |
bit offset |
data type |
allowed values |
default value |
acc. restr. |
mod. other var. |
excl. from DS |
name |
description |
1 |
0 |
Boolean |
false = Inactive, true = Active |
|
|
|
|
Reserved |
|
2 |
1 |
Boolean |
false = Inactive, true = Active |
false |
|
|
|
Warning Threshold Underrun |
Active: the process data value is below the configured lower value of the warning threshold. |
3 |
2 |
Boolean |
false = Inactive, true = Active |
false |
|
|
|
Warning Threshold Overrun |
Active: the process data value is above the configured upper value of the warning threshold. |
4 |
3 |
Boolean |
false = Inactive, true = Active |
false |
|
|
|
Temperature Overrun |
Active: the device ambient temperature is above the specified temperature range. |
5 |
4 |
Boolean |
false = Inactive, true = Active |
false |
|
|
|
Supply Voltage Overrun |
Active: the supply voltage is Ub > 30V. |
6 |
5 |
Boolean |
false = Inactive, true = Active |
false |
|
|
|
Supply Voltage Underrun |
Active: the supply voltage is Ub < 18V. |
7 |
6 |
Boolean |
false = Inactive, true = Active |
|
|
|
|
Reserved |
|
8 |
7 |
Boolean |
false = Inactive, true = Active |
|
|
|
|
Reserved |
|
9 |
8 |
Boolean |
false = Inactive, true = Active |
|
|
|
|
Reserved |
|
10 |
9 |
Boolean |
false = Inactive, true = Active |
|
|
|
|
Reserved |
|
11 |
10 |
Boolean |
false = Inactive, true = Active |
false |
|
|
|
Wire Break |
Active: the current loop to the connected device is interrupted. |
12 |
11 |
Boolean |
false = Inactive, true = Active |
|
|
|
|
Reserved |
|
13 |
12 |
Boolean |
false = Inactive, true = Active |
|
|
|
|
Reserved |
|
14 |
13 |
Boolean |
false = Inactive, true = Active |
|
|
|
|
Reserved |
|
15 |
14 |
Boolean |
false = Inactive, true = Active |
false |
|
|
|
Analog Input Underrun |
Active: the analog input value is below the nominal range. |
16 |
15 |
Boolean |
false = Inactive, true = Active |
false |
|
|
|
Analog Input Overrun |
Active: the analog input value is above the nominal range. |
Code | Additional code | Name | Description |
128 (0x80) | 17 (0x11) | Index not available | Read or write access attempt to a non-existing index. |
128 (0x80) | 18 (0x12) | Subindex not available | Read or write access attempt to a non-existing subindex of an existing index. |
128 (0x80) | 32 (0x20) | Service temporarily not available | Parameter not accessible due to the current state of the technology-specific application. |
128 (0x80) | 33 (0x21) | Service temporarily unavailable - local control | Parameter not accessible. The device is currently in an ongoing, locally controlled operation. |
128 (0x80) | 34 (0x22) | Service temporarily unavailable - device control | Parameter not accessible. The technology-specific application is currently in a remotely triggered operation. |
128 (0x80) | 35 (0x23) | Access denied | Write access to a read-only parameter or read access to write-only parameter. |
128 (0x80) | 48 (0x30) | Parameter value out of range | Written parameter value is outside of the permitted value range. |
128 (0x80) | 49 (0x31) | Parameter value above limit | Written parameter value is above its specified value range. |
128 (0x80) | 50 (0x32) | Parameter value below limit | Written parameter value is below its specified value range. |
128 (0x80) | 51 (0x33) | Parameter length overrun | Written parameter is longer than specified. |
128 (0x80) | 52 (0x34) | Parameter length underrun | Written parameter is shorter than specified. |
128 (0x80) | 53 (0x35) | Function unavailable | Written command is not supported by the technology-specific application. |
128 (0x80) | 54 (0x36) | Function temporarily unavailable | Written command is unavailable due to the current state of the technology-specific application. |
128 (0x80) | 64 (0x40) | Invalid parameter set | Written single parameter value collides with other existing parameter settings. |
128 (0x80) | 65 (0x41) | Inconsistent parameter set | Parameter set inconsistencies at the end of block parameter transfer. Device plausibility check failed. |
Code | Type | Name | Description |
6144 (0x1800) | Error | Invalid factory data | Device error - Exchange device. |
6145 (0x1801) | Error | Invalid parameter data | Device error - Exchange device. |
6146 (0x1802) | Warning | Warning threshold underrun | Application warning - The process data value is below the configured lower value of the warning threshold. Take according actions specific to the application setup. |
6147 (0x1803) | Warning | Warning threshold overrun | Application warning - The process data value is above the configured upper value of the warning threshold. Take according actions specific to the application setup. |
6149 (0x1805) | Warning | Analog input overrun | Application warning - The analog input signal is above the nominal range. Check boundaries of nominal range. |
6150 (0x1806) | Warning | Analog input underrun | Application warning - The analog input signal is below the nominal range. Check boundaries of nominal range. |
16912 (0x4210) | Warning | Device temperature overrun | Clear source of heat |
20752 (0x5110) | Warning | Primary supply voltage overrun | Check valid voltage range |
20753 (0x5111) | Warning | Primary supply voltage underrun | Check valid voltage range |
25376 (0x6320) | Error | Parameter error | Check datasheet and values |
30464 (0x7700) | Error | Wire break of a subordinate device | Check installation |
Parameters Menu |
Operating Parameter |
V_XPFA_IO_RTDType, ro |
V_XPFA_IO_WireMode, ro |
V_XPFA_Eval_Filter, ro |
V_XPFA_Eval_NotchFilter, ro |
|
Event Configuration |
V_XPFA_Event_Config.Temperature Overrun, ro |
V_XPFA_Event_Config.Supply Voltage Overrun, ro |
V_XPFA_Event_Config.Supply Voltage Underrun, ro |
V_XPFA_Event_Config.Wire Break, ro |
V_XPFA_Event_Config.Analog Input Underrun, ro |
V_XPFA_Event_Config.Analog Input Overrun, ro |
If V_XPFA_IO_RTDType = 19:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.01 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun, ro |
V_XPFA_Event_Thresh_High * 0.01 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun, ro |
|
If V_XPFA_IO_RTDType = 20:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun, ro |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun, ro |
|
If V_XPFA_IO_RTDType = 21:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun, ro |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun, ro |
|
If V_XPFA_IO_RTDType = 22:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun, ro |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun, ro |
|
If V_XPFA_IO_RTDType = 23:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun, ro |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun, ro |
|
If V_XPFA_IO_RTDType = 24:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1085069 + 0 Ω, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun, ro |
V_XPFA_Event_Thresh_High * 0.1085069 + 0 Ω, ro Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun, ro |
|
|
Observation Menu |
V_DeviceStatus |
V_ProcessDataInput, Dec.0 |
V_ProcessDataInput, Hex |
If V_XPFA_IO_RTDType = 19:
Analog Input - Temperature |
V_ProcessDataInput * 0.01 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 20:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 21:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 22:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 23:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 24:
Analog Input - Resistance |
V_ProcessDataInput * 0.1085069 + 0 Ω, Dec.2 |
|
Parameters Menu |
Operating Parameter |
V_XPFA_IO_RTDType |
V_XPFA_IO_WireMode |
V_XPFA_Eval_Filter |
V_XPFA_Eval_NotchFilter |
|
Event Configuration |
V_XPFA_Event_Config.Temperature Overrun |
V_XPFA_Event_Config.Supply Voltage Overrun |
V_XPFA_Event_Config.Supply Voltage Underrun |
V_XPFA_Event_Config.Wire Break |
V_XPFA_Event_Config.Analog Input Underrun |
V_XPFA_Event_Config.Analog Input Overrun |
If V_XPFA_IO_RTDType = 19:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.01 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.01 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 20:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 21:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 22:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 23:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 24:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1085069 + 0 Ω, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1085069 + 0 Ω, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
|
General Settings |
V_SystemCommand, Button:=130 Description=The parameter of the device are reset to factory settings. Note: A download of the data storage may be executed on the next power cycle and overwrite the factory default settings! |
V_SystemCommand, Button:=128 Description=A warm start is triggered and the device will be set to an initial state. The communication will be interrupted by the device and then reinitiated by the master. |
|
Observation Menu |
V_DeviceStatus |
V_ProcessDataInput, Dec.0 |
V_ProcessDataInput, Hex |
If V_XPFA_IO_RTDType = 19:
Analog Input - Temperature |
V_ProcessDataInput * 0.01 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 20:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 21:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 22:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 23:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 24:
Analog Input - Resistance |
V_ProcessDataInput * 0.1085069 + 0 Ω, Dec.2 |
|
Parameters Menu |
Operating Parameter |
V_XPFA_IO_RTDType |
V_XPFA_IO_WireMode |
V_XPFA_Eval_Filter |
V_XPFA_Eval_NotchFilter |
|
Event Configuration |
V_XPFA_Event_Config.Temperature Overrun |
V_XPFA_Event_Config.Supply Voltage Overrun |
V_XPFA_Event_Config.Supply Voltage Underrun |
V_XPFA_Event_Config.Wire Break |
V_XPFA_Event_Config.Analog Input Underrun |
V_XPFA_Event_Config.Analog Input Overrun |
If V_XPFA_IO_RTDType = 19:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.01 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.01 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 20:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 21:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 22:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 23:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1 + 0 °C, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
If V_XPFA_IO_RTDType = 24:
Application Specific Settings |
V_XPFA_Event_Thresh_Low * 0.1085069 + 0 Ω, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Underrun |
V_XPFA_Event_Thresh_High * 0.1085069 + 0 Ω, Dec.2 |
V_XPFA_Event_Config.Warning Threshold Overrun |
|
|
General Settings |
V_SystemCommand, Button:=130 Description=The parameter of the device are reset to factory settings. Note: A download of the data storage may be executed on the next power cycle and overwrite the factory default settings! |
V_SystemCommand, Button:=128 Description=A warm start is triggered and the device will be set to an initial state. The communication will be interrupted by the device and then reinitiated by the master. |
|
Observation Menu |
V_DeviceStatus |
V_ProcessDataInput, Dec.0 |
V_ProcessDataInput, Hex |
If V_XPFA_IO_RTDType = 19:
Analog Input - Temperature |
V_ProcessDataInput * 0.01 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 20:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 21:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 22:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 23:
Analog Input - Temperature |
V_ProcessDataInput * 0.1 + 0 °C, Dec.2 |
|
If V_XPFA_IO_RTDType = 24:
Analog Input - Resistance |
V_ProcessDataInput * 0.1085069 + 0 Ω, Dec.2 |
|
Note: This page shows the content of an IODD file transformed into HTML format. In the case of disparity between this and the XML view, the content of the XML file takes precedence.
Created by IODD Viewer V1.4.