Page 264 - SENSORS AND SYSTEMS | PEPPERL+FUCHS

262
Date of issue: 07/30/2012
Proximity Sensors,
Inductive Sensors,
slot types
1
.1.3
Electrical Connection
For detailed data and product description refer to the data sheets at
Technical Data
Germany: +49 621 776-4411
Consider the General Notes on the Information in the Pepperl+Fuchs Product Catalogs
Pepperl+Fuchs Group
fa-info@de.pepperl-fuchs.com
USA: +1 330 486 0001
fa-info@us.pepperl-fuchs.com
Singapore: +65 6779 9091
fa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
H
L
W
G
lc
General Data
Slot width
3.5
mm
Depth of immersion (lateral)
5 ... 7
typ. 6 mm
Type of voltage
DC
Nominal voltage
8
V
Suitable for 2:1 technology
,
with reverse polarity protection diode
Housing material
PBT
Protection degree
IP67
Connection type
flexible leads LIY , 500 mm
Model Number
SJ3,5-SN
SJ3,5-S1N
Switching element function
NAMUR, NO
NAMUR, NC
Current consumption
Measuring plate not detected
3
mA
1
mA
Measuring plate detected
3
mA
1
mA
Switching frequency
0 ... 2500
Hz
0 ... 3000
Hz
Ambient temperature
-25 ... 100
°C (-13 ... 212 °F)
-50 ... 100
°C (-58 ... 212 °F)
Use in the Hazardous Area
Use in the hazardous area
see instruction manuals
Category
1
G; 2G; 3G; 1D
Approvals and Certificates
Control drawing
116-0165
F
UL approval
cULus Listed, General Purpose
CSA approval
cCSAus Listed, General Purpose
CCC approval
Products with a maximum operating voltage of
36
V do not bear a CCC
marking because they do not require approval.
Dimensions
Length L [mm]
10
Width W [mm]
19
Height H [mm]
15
Slot width G [mm]
3.5
Connector area l
c
[
mm]
0
Inductive slot sensor
3.5
mm slot width (NAMUR with safety function)
3.5
mm slot width
Very fast response
DC, 2-wire NAMUR
Flexible leads version
EX approval 1G/1D for use up to
zone 0 / zone 20
Applicable up to SIL3 acc. to IEC
61508
Properties
Your Benefit
RD
L+
L-
GN
BN
L+
L-
BU
SJ3,5-S1N
SJ3,5-SN
0102