Page 868 - SENSORS AND SYSTEMS | PEPPERL+FUCHS

866
Date of issue: 0801/2012
AS-Interface,
Safety at Work
7
.3
For detailed data and product description refer to the data sheets at
Technical Data
Germany: +49 621 776-4411
Subject to modifications without notice
Pepperl+Fuchs Group
fa-info@pepperl-fuchs.com
USA: +1 330 486 0001
fa-info@us.pepperl-fuchs.com
Singapore: +65 6779 9091
fa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
H
L
W
Model Number
VAA-2E-G4-SE
Slave type
Safety-Slave
AS-Interface specification
V2.1
Required master specification
V2.0
Response delay
10
ms
Safety Integrity Level (SIL)
SIL 3
Performance level (PL)
PL e
Category
Cat. 4
MTTF
d
1500
a
Mission Time (T
M
)
10
a
PFH
d
1.54
E-9
PFD
2.5
E-5
Diagnostic Coverage (DC)
99.4 %
Rated operational current
30
mA
Number/Type
2
inputs for a 2-channel active optoelectronic protective devices
(
AOPD) for safeguarding positions and areas of danger up to
Type 4 in accordance with EN 61496-1.
Supply
from external auxiliary voltage U
AUX
Current loading capacity
2
A overload and short-circuit resistant
Input current
45
mA
Profile
S-0.B
Functional safety
EN 61496-1:2004/A1:2008 (by type 4), EN ISO 13849-1:2008
(
up to PL e), EN 61508:2001 and IEC 62061:2005 (up to SIL3)
Ambient temperature
-25 ... 55
°C (-13 ... 131 °F)
Protection degree
IP67
Mounting
DIN rail or screw mounting
Dimensions
Length L [mm]
102
Width W [mm]
45
Height H [mm]
51
VBP-HH1-V3.0-KIT
AS-Interface Handheld with accessory
VBP-HH1-V3.0
AS-Interface Handheld
VAZ-G4-B
Blind plug PG7
SLPCM8-2
Safety light grid with integrated control unit
VAZ-G4-B1
Blind plug M12
This and more accessories can be found in chapter 7.6 from page 893
See pages from 974 ... for cordsets
See pages 1074 ... for mounting aids
Accessories
AS-Interface safety module
2
inputs for 2-channel active
optoelectronic protective devices
SIL 3 / Ple
IP67
Modular solution to connect all
semiconductor safety devices
PG gland connection allows
cut-to-length cable
Properties
Your Benefit
SAFETYATWORK
TÜV approved
up tocat.4 /SIL3