Page 869 - SENSORS AND SYSTEMS | PEPPERL+FUCHS

Germany: +49 621 776-4411
Subject to modifications without notice
Pepperl+Fuchs Group
fa-info@pepperl-fuchs.com
USA: +1 330 486 0001
fa-info@us.pepperl-fuchs.com
Singapore: +65 6779 9091
fa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Date of issue: 0731/2012
867
For detailed data and product description refer to the data sheets at
AS-Interface,
Safety at Work
7
.3
Technical Data
H
L
W
General Data
Slave type
Safety-Slave
AS-Interface specification
V3.0
Required master specification
V2.1
Performance level (PL)
PL e
Category
Cat. 4
Safety Integrity Level (SIL)
SIL 3
Supply
from AS-Interface
Voltage
20 ... 30
V DC pulsed
Rated operational current
90
mA
Current loading capacity
input current limited
15
mA,
overload and short-circuit resistant
Inputs
Number/Type
2
safety-related inputs for mechanical contacts, crossed-circuit monitored:
2
single-channel contacts: up to category 2/PL c to ISO 13849-1 or
1 2-
channel contact: up to category 4/PL e to ISO 13849-1
Cable length must not exceed 30 m per input.
Outputs
Number/Type
1
conventional electronic output, PNP
Supply
from AS-Interface
Current
50
mA, short-circuit/overload protected
Profile
S-7.B
Ambient temperature
-25 ... 60
°C (-13 ... 140 °F)
Protection degree
IP67
Functional safety
EN ISO 13849-1:2008, IEC 62061:2005
Cable length
1
m
Model Number
VAA-2E1A-G10-SAJ/EA2J-1M
VAA-2E1A-G10-SAJ/EA2J-2X1M
Electrical connection
2
open cable ends:
1
open cable end for inputs
1
open cable end for output
1
open cable end for inputs and output
Dimensions
Length L [mm]
40,5
Width W [mm]
27,7
Height H [mm]
21,5
VBP-HH1-V3.0-KIT
AS-Interface Handheld with accessory
VBP-HH1-V3.0
AS-Interface Handheld
VAZ-PK-FK-0.2-V1-W
Connection cable G10 module/hand-held programming device
VAZ-2E1A-F85A-S
Emergency stop button
This and more accessories can be found in chapter 7.6 from page 893
See pages from 974 ... for cordsets
See pages 1074 ... for mounting aids
Accessories
AS-Interface safety modules
2
safety-related inputs for mechani-
cal contacts
SIL 3 / Ple
IP67
Reduces installation complexity
and cost by interfacing with any
dry-contact safety device
Integrated non-safe output drives
announciation
(
horns/visual indicators)
Properties
Your Benefit
SAFETYATWORK
TÜV approved
up tocat.4 /SIL3