868
Date of issue: 0801/2012
AS-Interface,
Safety at Work
7
.3
For detailed data and product description refer to the data sheets at
Technical Data
Germany: +49 621 776-4411
Subject to modifications without notice
Pepperl+Fuchs Group
fa-info@pepperl-fuchs.com
USA: +1 330 486 0001
fa-info@us.pepperl-fuchs.com
Singapore: +65 6779 9091
fa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
H
L
W
Model Number
VAA-2E2A-G12-SAJ/EA2L
Slave type
Safety-Slave
AS-Interface specification
V2.1
Required master specification
V2.1
Safety Integrity Level (SIL)
SIL 3
UL File Number
E87056
Rated operational current
50
mA
Supply
from AS-Interface
Voltage
20 ... 30
V DC pulsed
Current loading capacity
input current limited
15
mA,
overload and short-circuit resistant
Inputs
Number/Type
2
safety-related inputs for mechanical contacts, crossed-circuit monitored:
2
single-channel contacts: up to category 2/PL c to ISO 13849-1 or
1 2-
channel contact: up to category 4/PL e to ISO 13849-1 nicht uebersetzt!
Outputs
Number/Type
2
conventional electronic outputs, PNP
Supply
from external auxiliary voltage U
AUX
Current
1.5
A per output, short-circuit protected
Functional safety
ISO 13849-1 (up to category 4/PL e), IEC 61508/IEC 62061 (up to SIL3)
Mounting
Mounting base
Profile
S-7.B
Ambient temperature
-25 ... 60
°C (-13 ... 140 °F)
Protection degree
IP67
Dimensions
Length L [mm]
118
Width W [mm]
57,4
Height H [mm]
35
VAZ-V1-B2
Blind plug for M12 sockets
VBP-HH1-V3.0-KIT
AS-Interface Handheld with accessory
VAZ-G12-MARK1-YE
Lettering set for AS-Interface module, design G12 "Safety, short", yellow
VBP-HH1-V3.0
AS-Interface Handheld
VAZ-PK-1,5M-V1-G
Connection cable module/hand-held programming device
VAZ-V1-B
Blind plug for M12 sockets
VAZ-CLIP-G12
lock for G12 module
This and more accessories can be found in chapter 7.6 from page 893
See pages from 974 ... for cordsets
See pages 1074 ... for mounting aids
Accessories
AS-Interface safety modules
2
safety-related inputs for mechani-
cal contacts
SIL 3 / Ple
IP67
Safety module with all the benefits
of the G12 line
Flexible solution with inputs for
any dry-contact safety device and
non-safe output for machine
control or annunciation
Properties
Your Benefit
SAFETYATWORK
TÜV approved
up tocat.4 /SIL3