964
Germany: +49 621 776-4411
Refer to General Notes Relating to Product Information
Pepperl+Fuchs Group
USA: +1 330 486 0001
Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Logic Control Units,
Sensor Output Converters
9
.5
Technical Data
For detailed data and product description refer to the data sheets at
Electrical Connection
General Data
LED yellow
Output state
lead breakage: LED off, output locked
Operating voltage
10 ... 30 V DC
Operating current
approx. 22 mA
Sensor supply
8 V DC
Input
Connection
terminals 1+, 2-
Connectable sensor types NAMUR
Output
Current
200 mA short-circuit protected
Ambient temperature
-25 ... 70 °C (-13 ... 158 °F)
Storage temperature
-25 ... 85 °C (-13 ... 185 °F)
Connection
self-opening apparatus connection terminals,
max. core cross-section 0.34 ... 2.5 mm
2
Dimensions
20 x 60 x 40 (in mm)
Model Number
KCD2-EL
KCD2-E2L
Output
Output type
1 NPN, NO
1 PNP, NO
Connection
terminal 4+
terminal 4-
Signal level
U
B
- 1.1V
U
B
- 1.8V
Sensor output interface terminal
Sensor output interface terminal
DC supply voltage
Converts Namur to 3-wire DC
Short circuit proof output
Lead break detection
Properties
Supply
voltage
Output
Input
Lead breakage
monitoring
Sensor
I≤
0.1mA
5+ 6-
4-
1+
1+
2-
1+
2-
3
3
5+ 6-
4+
1+
1+
2-
1+
2-
3
3
I≤
0.1mA
Supply
voltage
Output
Input
Lead breakage
monitoring
Sensor
KCD2-EL
KCD2-E2L
1...,956,957,958,959,960,961,962,963,964,965 967,968,969,970,971,972,973,974,975,976,...1124