325
Germany: +49 621 776-4411
Refer to General Notes Relating to Product Information
Pepperl+Fuchs Group
USA: +1 330 486 0001
Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Proximity Sensors,
Inductive Sensors,
slot type
1
.1.3
Technical Data
For detailed data and product description refer to the data sheets at
Electrical Connection
H
W
L
lc
G
Danger!
In safety-related applications the sensor must be operated with a qualified fail safe interface from
Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the "exida Functional Safety Assessment" document which is available on
as an integral part of this product’s documentation.
General Data
Slot width
2 mm
Lateral immersion switchpoint
5 ... 7 typ. 6 mm
Type of voltage
DC
Nominal voltage
8 V
Switching frequency
0 ... 5000 Hz
Suitable for 2:1 technology
✔
, with reverse polarity protection diode
Housing material
PBT
Protection degree
IP67
Connection type
flexible leads LIFYW , 500 mm
Model Number
SJ2-SN
SJ2-S1N
Output type
NAMUR, NO
●
NAMUR, NC
●
Current consumption
Measuring plate not detected
3 mA
●
1 mA
●
Measuring plate detected
3 mA
●
1 mA
●
Ambient temperature
-25 ... 100 °C (-13 ... 212 °F)
●
-40 ... 100 °C (-40 ... 212 °F)
●
Use in the Hazardous Area
Use in the hazardous area
see instruction manuals
●
●
Category
1G; 2G; 3G; 1D
●
●
Approvals and Certificates
FM control drawing
116-0165F
●
●
UL approval
cULus Listed, General Purpose
●
●
CSA approval
cCSAus Listed, General Purpose
●
●
CCC approval
CCC approval / marking not required for sensors rated
36 V
Dimensions
Length L [mm]
15
Width W [mm]
8
Height H [mm]
12
Slot width G [mm]
2
Connector length l
c
[mm]
0
Inductive slot sensor
2 mm slot width (NAMUR with safety function)
Application Note:
Reference appendix, data sheet,
operating instructions, and appropriate standards.
To be used within the electrical, environmental, and
mechanical limitations of the device and area.
2 mm slot width
Fast response time
NAMUR output
Flexible leads version
EX approval 1G/1D for use up to
zone 0 / zone 20
FM Class and Division approvals
Applicable up to SIL3 acc. to IEC
61508
Properties
Benefits
RD
L+
L-
GN
BN
L+
L-
BU
SJ2-S1N
SJ2-SN
0102