878
Germany: +49 621 776-4411
Refer to General Notes Relating to Product Information
Pepperl+Fuchs Group
USA: +1 330 486 0001
Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
AS-Interface,
Safety at Work
7
.3
Technical Data
For detailed data and product description refer to the data sheets at
W
L
H
General Data
AS-Interface specification
V3.0
Performance level (PL)
PL e
Safety Integrity Level (SIL)
SIL 3
Mission Time (T
M
)
20 a
Ambient temperature
0 ... 55 °C (32 ... 131 °F)
Protection degree
IP20
Mounting
DIN rail
Model Number
VAS-2A8L-KE4-8SE
VBA-2E-KE4-ENC-S
Type
Safety monitor
Safety module
Required master specification
V2.1
V3.0
PFH
d
2.77 E-9
5.08 E-9
Rated operating current
150 mA from AS-Interface;
200 mA from AUX
200 mA from AS-Interface;
4 A from AUX
Inputs
Number/Type
4 safe inputs CAT 4 or
8 standard inputs and outputs
2 inputs for incremental rotary encoders
AMP mini-IO connector
Supply
24 V U
AUX
Voltage
U
b
= 5 V DC
Current loading capacity
10 mA per standard output
0.7 A per OSSD
Input current
Static switching current 4 mA at 24 V,
dynamic 30 mA at 24 V (T=100
s)
Outputs
Number/Type
2/electronic safe
Supply
from external auxiliary power U
AUX
Profile
S-0.B.E
Safe input slaves: S-0.B.E
Diagnosis slaves: S-7.A.5.
Dimensions
Length L [mm]
113
Width W [mm]
22,5
Height H [mm]
99
VBP-HH1-V3.0-KIT-110V
AS-Interface Handheld with accessory
VBP-HH1-V3.0-110V
AS-Interface Handheld
VAZ-SIMON-USB
Connection cable module/hand-held programming device
VAZ-ENC-1,5M-PVC
Connection cable for connecting encoders to a speed monitor
RVS58S-*******Z
Incremental rotary encoder
RVS58S-282YYR4ZN-01024
Safety incremental encoder
These and more accessories can be found in chapter 7.6 from page 905
See pages from 970 ... for cordsets
See pages 1066 ... for mounting accessories
Accessories
AS-Interface safety monitor / module
Versions with 2 safety-related
inputs for mechanical contacts, 8 /
4 safe inputs Cat. 4, 2 inputs for
incremental rotary encoders and 1
safety relay output
SIL 3 / Ple
IP20
VAS-2A8L-KE4-8SE
Safety monitor with two integrated
safe electronic outputs offers
decentralized safety control
Chip card makes device
replacement fast and easy
Integrated mini-safety PLC
functionality make this the ideal
solution for small to medium size
stand-alone applications
VBA-2E-KE4-ENC-S
Safe, fully configurable 2-channel
zero-speed monitor makes zero-
speed detection over AS-Interface
flexible and convenient
Properties
Benefits
62
Spec 2.1