VAA-2E-G4-SE
Slave type
Safety-Slave
AS-Interface specification
V2.1
Required master specification
V2.0
Response delay
10 ms
Safety Integrity Level (SIL)
SIL 3
Performance level (PL)
PL e
Category
Cat. 4
MTTF
d
1500 a
Mission Time (T
M
)
10 a
PFH
d
1.54 E-9
PFD
2.5 E-5
Diagnostic Coverage (DC)
99.4 %
Rated operating current
30 mA
Number/Type
2 inputs for a 2-channel active optoelectronic protective devices
Supply
from external auxiliary power U
AUX
Current loading capacity
2 A overload and short-circuit resistant
Input current
45 mA
Profile
S-0.B
Functional safety
EN 61496-1:2004/A1:2008 (by type 4), EN ISO 13849-1:2008 (up to
PL e), EN 61508:2001 and IEC 62061:2005 (up to SIL3)
Ambient temperature
-25 ... 55 °C (-13 ... 131 °F)
Protection degree
IP67
Mounting
DIN rail or screw mounting
Dimensions
Length L [mm]
102
Width W [mm]
45
Height H [mm]
51
VBP-HH1-V3.0-KIT-110V
AS-Interface Handheld with accessory
VBP-HH1-V3.0-110V
AS-Interface Handheld
SLPCM8-2
Safety light grid with integrated control unit
VAZ-G4-B1
Blind plug M12
These and more accessories can be found in chapter 7.6 from page 905
See pages from 970 ... for cordsets
See pages 1066 ... for mounting accessories
Accessories
AS-Interface safety module
2 inputs for 2-channel active
optoelectronic protective devices
SIL 3 / Ple
IP67
Modular solution to connect all
semiconductor safety devices
M12 gland connection allows
cut-to-length cable
Properties
Benefits
TÜV approved
up tocat.4 /SIL3