230
Germany: +49 621 776-4411
Refer to General Notes Relating to Product Information
Pepperl+Fuchs Group
USA: +1 330 486 0001
Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Proximity Sensors,
Inductive Sensors,
cylindrical
1
.1.1
Technical Data
For detailed data and product description refer to the data sheets at
Electrical Connection
D
L
Pos. A
Pos. B
Pos. C
lc
l1
lt
General Data
Rated operating distance
1.5 mm
Installation
flush
Output type
NAMUR, NC
Nominal voltage
8.2 V (R
i
approx. 1 k
)
Current consumption
Measuring plate not detected
3 mA
Measuring plate detected
1 mA
Switching frequency
0 ... 400 Hz
Ambient temperature
-25 ... 85 °C (-13 ... 185 °F)
Housing material
Stainless steel 1.4305 / AISI 303
Model Number
NJ1,5-18GM-N-D
NJ1,5-18GM-N-D-V1
Protection degree
IP66 / IP68
IP67
Connection type
Connector M12 x 1 , 4-pin
cable PVC , 2 m
Use in the Hazardous Area
Use in the hazardous area
see instruction manuals
Category
2G; 1D
Approvals and Certificates
UL approval
cULus Listed, General Purpose
CSA approval
cCSAus Listed, General Purpose
CCC approval
CCC approval / marking not required for sensors rated
36 V
Dimensions
Length L [mm]
50
45
Diameter D [mm]
M18 x 1
Thread length l
t
[mm]
20
Cap length l
1
[mm]
15
Connector length l
c
[mm]
0
10
LED position
-
V1-G
4-pin, M12 female field-attachable connector, straight
V1-W
4-pin, M12 female field-attachable connector, angled
V1-W-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable, angled
V1-G-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable, straight
KCD2-SR-Ex2
2-channel isolated amplifier
For detailed information on isolated amplifiers refer to the data sheets at
These and more accessories can be found in chapter 10
See pages from 970 ... for cordsets See pages 1066 ... for mounting accessories
Accessories
Inductive sensor
cylindrical, Ø 18 mm (NAMUR)
Application Note:
Reference appendix, data sheet,
operating instructions, and appropriate standards.
To be used within the electrical, environmental, and
mechanical limitations of the device and area.
Ø18 mm housing
1.5 mm flush mountable
NAMUR output
Cable and connector versions
ATEX approved sensor applicable
up to zone 0 and zone 20
Intrinsically safe when connected
to approved device
FM Class and Division approvals
Compression proof up to 350 bar,
dynamically on active surface
Properties
Benefits
1
L+
L-
2
BN
L+
L-
BU
NJ1,5-18GM-N-D-V1
NJ1,5-18GM-N-D
1
3
4
2
1
BN
2
BU
Wire colors in accordance with EN 60947-5-6
(brown)
(blue)
0102
1...,222,223,224,225,226,227,228,229,230,231 233,234,235,236,237,238,239,240,241,242,...1124