231
Germany: +49 621 776-4411
Refer to General Notes Relating to Product Information
Pepperl+Fuchs Group
USA: +1 330 486 0001
Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Proximity Sensors,
Inductive Sensors,
cylindrical
1
.1.1
Technical Data
For detailed data and product description refer to the data sheets at
Electrical Connection
D
L
Pos. A
Pos. B
Pos. C
lc
l1
lt
General Data
Output type
NAMUR, NC
Nominal voltage
8.2 V (R
i
approx. 1 k
)
Current consumption
Measuring plate not detected
3 mA
Measuring plate detected
1 mA
Switching frequency
0 ... 2000 Hz
Ambient temperature
-25 ... 100 °C (-13 ... 212 °F)
Protection degree
IP68
Connection type
cable PVC , 2 m
Model Number
NJ6-22-N
NJ6-22-N-G
NJ10-22-N
NJ10-22-N-G
Rated operating distance
10 mm
● ●
6 mm
● ●
Installation
flush
● ●
non-flush
● ●
Housing material
Stainless steel 1.4305 / AISI 303
PBT
Use in the Hazardous Area
Use in the hazardous area
see instruction manuals
● ● ● ●
Category
2G
2G; 1D
2G; 3G
2G; 3G; 3D
Approvals and Certificates
FM control drawing
116-0165F
UL approval
cULus Listed, General Purpose
● ● ● ●
CSA approval
cCSAus Listed, General Purpose
● ● ● ●
CCC approval
CCC approval / marking not required for sensors rated
36 V
Dimensions
Length L [mm]
35
Diameter D [mm]
22
PG21
22 PG21
Thread length l
t
[mm]
0
35
0
15
Cap length l
1
[mm]
0
20
Connector length l
c
[mm]
0
LED position
-
KCD2-SR-Ex2
2-channel isolated amplifier
For detailed information on isolated amplifiers refer to the data sheets at
These and more accessories can be found in chapter 10
See pages from 970 ... for cordsets See pages 1066 ... for mounting accessories
Accessories
Inductive sensor
cylindrical, Ø 22/28.3 mm (NAMUR)
Application Note:
Reference appendix, data sheet,
operating instructions, and appropriate standards.
To be used within the electrical, environmental, and
mechanical limitations of the device and area.
Ø22 mm smooth and threaded
housing versions
6 mm and 8 mm sensing ranges
NAMUR output
Cable version
ATEX approved sensors applicable
up to zone 1 and zone 20
Intrinsically safe when connected
to approved device
FM Class and Division approvals
Properties
Benefits
BN
L+
L-
BU
NJ10-22-N
NJ10-22-N-G
NJ6-22-N
NJ6-22-N-G
0102