311
Germany: +49 621 776-4411
Refer to General Notes Relating to Product Information
Pepperl+Fuchs Group
USA: +1 330 486 0001
Singapore: +65 6779 9091
Copyright Pepperl+Fuchs
Proximity Sensors,
Inductive Sensors,
rectangular types
1
.1.2
Technical Data
For detailed data and product description refer to the data sheets at
Electrical Connection
W
L
H
lc
General Data
Output type
NAMUR, NC
Type of voltage
DC
Nominal voltage
8.2 V (R
i
approx. 1 k
)
Current consumption
Measuring plate not detected
3 mA
Measuring plate detected
1 mA
Housing material
PBT/metal
Protection degree
IP67
Model Number
NJ50-FP-N-P4
NCB40-FP-N0-P4
NCN50-FP-N0-P4
NCN50-FP-N0-P4-V1
Rated operating distance
40 mm
50 mm
Installation
flush
non-flush
Switching frequency
0 ... 100 Hz
0 ... 80 Hz
Switching state indication
LED, yellow
Ambient temperature
-25 ... 100 °C (-13 ... 212 °F)
-25 ... 70 °C (-13 ... 158 °F)
Connection type
Connector M12 x 1 , 4-pin
screw terminals
Use in the Hazardous Area
Use in the hazardous area
see instruction manuals
Category
1G; 2G; 1D
Approvals and Certificates
FM Control drawing
116-0165F
UL approval
cULus Listed, General
Purpose
CSA approval
cCSAus Listed, General
Purpose
CCC approval
CCC approval / marking not required for sensors rated
36 V
Dimensions
Length L [mm]
80
Width W [mm]
80
Height H [mm]
40
Connector length l
c
[mm]
11
25
Connector thread
conduit entrance with
1/2" NPT opening
-
1/2"NPT-V1-G-S-.3M
Receptacle
1/2"NPT to
M12 x 1, 4-pin
V1-G
4-pin, M12 female field-attachable connector
V1-W
4-pin, M12 female field-attachable connector
V1-G-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable
V1-W-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable
KCD2-SR-Ex2
2-channel isolated amplifier
For detailed information on isolated amplifiers refer to the data sheets at
These and more accessories can be found in chapter 10
See pages from 970 ... for cordsets See pages 1066 ... for mounting accessories
Accessories
Inductive sensor
FP series (NAMUR)
Application Note:
Reference appendix, data sheet,
operating instructions, and appropriate standards.
To be used within the electrical, environmental, and
mechanical limitations of the device and area.
Flat pack housing
40 mm and 50 mm sensing ranges
NAMUR output
Terminal compartment and
connector versions
ATEX approval up to zone 0 / zone
20
Intrinsically safe when connected
to approved device
FM Class/Div approvals
Properties
Benefits
1
L+
L-
2
1
L+
L-
2
NCB40-FP-N0-P4
NCN50-FP-N0-P4
NJ50-FP-N-P4
NCN50-FP-N0-P4-V1
1
3
4
2
1
BN
2
BU
Wire colors in accordance with EN 60947-5-6
(brown)